Hardware Troubleshooting – HPC / Data Center Nodes


1. Identify Scope and Impact (Using OME)

Before taking any action, clearly identify the scope and impact of the issue.

Determine the Level of Impact

  • Node-level issue
  • Rack-level issue
  • Cluster-level issue
  • Check whether running jobs are impacted

⚠️ Important: If jobs are running on the node, do not touch the node until jobs are completed.


2. Check Workload Manager Status (PBS Pro)

First, verify node and job status from the scheduler.

Commands

qstat -aw
pbsnodes -aSj | grep <node-hostname>

What You Can Identify

  • Node state (free, busy, offline)
  • Jobs running on the node
  • Job owner and job ID

3. Handling Nodes with Running Jobs

If the node is hosting any jobs:

  1. Do not troubleshoot immediately
  2. Wait until job completion
  3. Inform the respective users / higher authorities
  4. After job completion, proceed with troubleshooting

Put Node in Offline Mode

pbsnodes -o <node-hostname> -C "hardware issue"

✔ This prevents new jobs from being scheduled on the node.


4. Check Cluster Health Status (Bright Cluster Manager)

Use Bright Cluster Manager (BCM) to verify node health.

Using cmsh

cmsh
device use <node-hostname>
status

Or:

cmsh
device list | grep <node-hostname>

Purpose

  • Identify node health status
  • Detect cluster-wide issues

5. Centralized Hardware Alert Check (OME)

OpenManage Enterprise (OME) acts as the single source of truth for Dell server hardware issues.

OME Provides Alerts For

  • CPU
  • DIMM (Memory)
  • PSU
  • FAN
  • Thermal warnings
  • Power supply redundancy
  • Firmware mismatches
  • Lifecycle controller logs

6. iDRAC Access for Node-Level Diagnosis

Using OME, access the iDRAC console of the affected node.

Using iDRAC, You Can Check

  • PSU status
  • Fan status
  • Inlet temperature
  • Fan RPMs
  • Node-level patterns
  • Port status
  • Power consumption status
  • Sensor health
  • System event logs (SEL)

📌 Tip: If multiple nodes in the same rack show failures, immediately suspect:

  • Power issues
  • Cooling issues

7. Power Drain (Cold Power Reset) Procedure

A power drain is recommended after identifying hardware issues.

Best Practice

Always collect logs first before performing a power drain.


8. Log Collection via iDRAC

Steps

  1. Login to iDRAC console
  2. Navigate to Maintenance → SupportAssist
  3. Click Start Log Collection
  4. Save logs for analysis or Dell support

9. Power Drain Procedure (System Mute / OFF-RPM)

Steps

  1. Remove network cables

  2. PowerSync cable

  3. InfiniBand (IB) cable
  4. iDRAC cable
  5. Remove power cables from both PSUs
  6. Remove any additional power cables (if connected)
  7. Press and hold the power button for 2–5 minutes

  8. This drains residual power completely


10. Power-On and Recheck

  1. Reconnect all cables
  2. Power ON the server
  3. Re-collect logs
  4. Observe iDRAC alerts
  5. If issue persists, raise a Dell support case with logs

11. Common Hardware Troubleshooting Scenarios

RAM Issue

  • Pop-up error in iDRAC
  • Scenario 1: Remove faulty DIMM
  • Scenario 2: Swap DIMM position
  • Replace DIMM if issue persists

InfiniBand (IB) Cable Issue

  • Try a different cable
  • Perform power drain
  • If issue persists, replace IB cable

PSU Issue

  • Swap PSU positions
  • Check redundancy status
  • Replace PSU if issue persists

iDRAC Access Issue

  • Reset iDRAC
  • Check BIOS/iDRAC settings
  • Replace iDRAC card if required

CPU Issue

  • Boot server with 1 CPU / 1 RAM
  • Identify faulty CPU
  • Proceed with replacement

Fan Issue

  • Swap fan positions
  • If issue follows the fan → replace fan

12. Final Step – Node Recovery

Once the issue is resolved:

pbsnodes -r <node-hostname>

✔ Node is now available for scheduling jobs.


13. Best Practices

  • Always check scheduler status first
  • Never disturb nodes with running jobs
  • Use OME as the authoritative source
  • Collect logs before power drain
  • Follow systematic isolation (swap & test)
  • Escalate to Dell support with logs if required